Quiz

image
Year 2024

December
Week # 2 Quiz 4

Q1. Calculate the protection trip time of the inverse definite minimum time (IDMT) overcurrent relay, according to IEC 60255 protection curves. Assume very inverse curve type, relay pickup current = 1kA, fault current = 10 kA and time-multiplier setting (TMS) = 1.

Q2. A 1-phase transmission line has an impedance (3+4j) Ω . Find the power factor of the load for achieving maximum voltage regulation?

Q3. If the severity of single line-to-ground fault at the terminals of an unloaded synchronous generator is lesser than that of 3-phase faults, then __________ where, \(X_1\) is the positive sequence reactance of the generator,\(X_{g0}\) is the zero sequence reactance of the generator and\(X_n\) is the neutral reactance.

Q4. If the real power flow through the uncompensated line is 1 pu and the degree of series compensation ‘K’ is 0.5, the power flow through the series compensated line is

Q5. A generating station having 'n' section busbars each rated at Q kVA with \(x \%\) reactance is connected on the tie-bars system through busbar reactances of b%. Determine the short-circuit kVA if a 3-phase fault takes place on one section.



Q6. A 183-bus power system has 150 PQ buses and 32 PV buses. In the general case, to obtain the load flow solution using Newton-Raphson method in polar coordinates, the minimum number of simultaneous equations to be solved is _____________.

Q7. The power generated by two plants are: \(P_1=50 MW, P_2 = 40 MW\). If the loss coefficients are \(B_{11}=0.001, B_{22}=0.0025, B_{12}=-0.0005\), then the power loss will be

Q8. A single line diagram of a power system is shown if Fig. The diagonal elements of the \(Z_{bus}\) matrix are



Q9. Consider two buses is connected by an impedance of \((0+j5)\Omega\) The bus 1 voltage is \(100 \angle 30 ^\circ\) V, and bus 2 voltage is \(100 \angle0 ^\circ\) V. The real and reactive power supplied by bus 1, respectively are (Consider power flowing from bus 1 to 2 as positive)

Q10. If the severity of single line-to-ground fault at the terminals of an unloded star connected synchronous generator is greater than that of 3-phase faults, then _______ where, \(X_1\) is the positive sequence reactance of the generator, \(X_{g0}\) is the zero sequence reactance of the generator and \(X_n\) is the neutral reactance.